Common problems and what to send to support

Manual — Data collectors · chapter 9 of 10

Almost every collector problem falls into one of three places: the computer does not talk to H2O (internet, proxy, token), the computer does not talk to the equipment (address, port, network) or the point is mapped wrong (register, type, scale). Start by finding out which of the three.

What the screen shows Where the problem is Go to
collector No contact, Access revoked or Not paired between the computer and H2O The collector does not talk to H2O
collector Running, asset No answer between the computer and the equipment The equipment does not answer
asset Reading, wrong value or silent point in the point The value is wrong
everything reading, but the ticket does not open (or opens too often) in the measurement or in the collector rule Tickets
Symptom Likely cause What to do
Windows protected your PC warning when opening the installer the installer does not yet have a signature recognised by Windows More info › Run anyway; use only the file downloaded through the H2O link or delivered by ATG
the installer does not open or asks for a password user without administrator rights right-click › Run as administrator, with an administrator user
Não foi possível parear com o H2O. (Could not pair with H2O.) token typed wrong, expired (24 hours), already used, or collector inactive; Ambiente de teste (Test environment) selected by mistake; no outbound HTTPS generate another token; check that Produção (o H2O do cliente) (Production (the customer’s H2O)) is selected; check the outbound HTTPS and the proxy with the IT team
installed, but the collector is still Not paired in H2O the token used belonged to another collector check the collector name in the tray icon menu; pair again with the token of the right collector (chapter 8)
warning that the service was not created or did not start antivirus or Windows policy blocked the service look at the end of coletor.log; ask the IT team to allow it; run the installer again
the Windows installer block does not appear in H2O there is no installer published in the environment, or the collector type is H2O Link Collector device check the Collector type; ask ATG for the installer
Symptom Likely cause What to do
No contact in H2O; on the computer, yellow icon Sem ligação com o H2O (No connection to H2O) internet went down, outbound HTTPS blocked or wrong proxy check with the IT team the outbound HTTPS to api.prod.atg.com.br and the proxy; allow h2o-coletor.exe in the firewall and in the antivirus. The readings are kept and go on when the connection returns
No contact in H2O; red icon Serviço parado (Service stopped) the service went down or was stopped right-click the icon › Reiniciar o serviço (administrador) (Restart the service (administrator)); if it goes down again, look at the end of coletor.log
No contact in H2O; no icon, computer not responding computer switched off, hibernating or off the network turn the computer on; disable sleep and hibernation in the Windows power options
Access revoked in H2O; red icon O H2O recusou o token deste coletor (H2O refused the token of this collector) someone clicked Revoke access pair again (chapter 8)
collector Running in H2O with the name of another computer; on this one, red icon O H2O recusou o token deste coletor another installation paired on the same collector if the other one is the right one, uninstall this one; if not, generate another token and pair this one again
Inactive in H2O Collector active was unchecked check Collector active on the Settings tab and save
grey icon Iniciando (Starting) for more than 2 minutes the service cannot write to the data folder check the permission of C:\ProgramData\H2O Coletor; run h2o-coletor.exe --estado at the prompt
tray icon does not appear someone closed the icon Start menu › H2O Link Coletor (ícone da bandeja) (tray icon); the collection does not depend on the icon
configuration N pending that does not change the collector did not fetch the new configuration Commands tab › Reload configuration; if the command expires without an answer, the problem is one of contact
commands stay Queued and become Expired without an answer the collector has no contact solve the contact; send the command again

The collector is Running, but the asset appears as No answer on the Equipment tab and in the Assets not answering card of the Health tab — with the error the collector received.

Likely cause How to check
wrong IP address or port in the link ping the IP from the collector computer; check the port: Modbus TCP 502, BACnet/IP 47808 (UDP), SNMP 161 (UDP), unless the equipment uses another one
equipment switched off or under maintenance look at the equipment; if it is going to take long, uncheck Enabled in the link so the alert leaves the bell
network without a route (different VLAN) or firewall on the way Discovery on the equipment range shows whether the collector can reach it (chapter 6); ask the IT team for the route or the clearance
wrong device id (Modbus), instance (BACnet) or community (SNMP) check on the display or in the equipment manual and correct it in Edit on the link
slow equipment or shared serial line increase the Timeout (ms) and the Pause between requests (ms) in Advanced
serial that does not read wrong COM port (the Windows Device Manager shows it), different baud rate or parity, A and B wires swapped on the RS-485
Symptom Likely cause What to do
absurd value (for example 1.2e+38) or always 0 wrong Data type or Byte order (float32 instead of int16, ABCD instead of CDAB) correct it in the point and check with Read now
value 10, 100 or 1000 times larger or smaller wrong Scale (multiplies) check the scale in the equipment manual
value of another quantity neighbouring register: the manual numbers from 1 and the Register (base 0) field starts at 0 subtract 1 from the register and check with Read now
Read now answers no answer the point address does not exist on the equipment, or wrong table (holding instead of input) check the table and the register in the manufacturer map
point in Silent points, asset Reading only that address fails Log tab, Error filter; correct the point address
measurement inactive or deleted below the point the asset metric was deactivated reactivate the metric on the Metering tab of the asset, or delete the point
readings arrive in a block, with past times the internet went down and came back: the collector kept and resent them normal. The Local cache, on the Health tab, shows how much is still to be sent
readings with the wrong time, or refused wrong computer clock set the clock and turn on the Windows automatic time synchronisation
Symptom Likely cause What to do
out-of-range reading and no ticket Open ticket on anomaly unchecked in the metric (a measurement created by the AI, by a model or by the discovery is born this way); metric without a range; Store only, do not open a ticket rule on the collector; reading older than the minutes of the rule check the metric on the Metering tab of the asset and the Late readings card of the collector (chapter 7)
the anomaly continues and no other ticket opens there is already an open ticket for that measurement it is the rule: one ticket per ongoing anomaly. See the follow-ups of the ticket
too many tickets from the same measurement the range is tight and the value fluctuates around the limit widen the metric range, or change What to send of the point to Average with a larger window
collector lost contact and did not open a ticket Open a ticket after unchecked, time not reached yet, or collector Inactive or revoked check the Ticket when contact is lost card. The bell warns anyway
the collector ticket did not close when it came back it is the rule: the return follow-up goes in and whoever handles it decides solve the ticket

If you need help from ATG, gather at once:

  • the name of the company, of the site and of the collector, as they appear in the list;
  • the status of the collector and what the Health tab shows (a screenshot is enough);
  • the program version — Version column of the list, or h2o-coletor.exe --versao on the computer;
  • what the tray icon says (colour and text);
  • the file C:\ProgramData\H2O Coletor\coletor.log — or the last 200 lines;
  • the file pontos.json in the same folder (the status of each point);
  • for a value problem: the asset, the point, what Read now showed and what the equipment display shows;
  • for an installation problem: the installer message, in full.