Linking assets and building the points
Manual — Data collectors · chapter 5 of 10
Telling the collector what to read takes two steps, both on the collector page: linking the asset (which equipment, with which protocol and at which address) and creating the points (which value to read from it and which measurement to store it in). The points can be typed one by one or built all at once — by the AI, from a library model or by copying from another asset.The collector page
Section titled “The collector page”Clicking a collector in the list opens its page: the name, the status badge, a line with the site, the type, the computer, the version and the last contact, and seven tabs.
| Tab | What it has | Chapter |
|---|---|---|
| Equipment | the linked assets, with protocol, address and status | 5 |
| Points | what is read from each asset and the measurement that receives each value | 5 |
| Discovery | the scan of the customer network | 6 |
| Health | network, cache, availability, outages, assets not answering and silent points | 7 |
| Commands | the requests sent to the collector and the answers | 7 |
| Log | what the collector logged | 7 |
| Settings | the collector record and the pairing | 3 and 8 |
Linking an asset
Section titled “Linking an asset”
Figure 5. The Equipment tab of the collector Coletor Windows (WINDESK), with the assets TR-01, UPS-02 and QD-TI-01 linked.
- 1The collector header: name, status and the line with site, type, computer, version and last contact.
- 2The tabs of the page.
- 3Link asset.
- 4Asset column: the name, the code and the site of the asset.
- 5Protocol and address column: how the collector reaches the equipment.
- 6Map column: where the points came from (built by hand, model, file, AI, copy or discovery).
- 7Points column: how many are reading, out of the total — for example “8 of 8”.
- 8Status and Last reading columns.
- 9The row actions: Points, Map with AI, Model, Edit and Unlink.
- On the Equipment tab, click Link asset.
- Choose the Asset type and then the Asset. The list brings only the assets of the collector site and of the selected subsites.
- In How the collector reaches it, choose the Protocol and fill in the fields that appear.
- If needed, adjust the Advanced block. Click Save.

Figure 6. The Link asset form, with the Modbus TCP protocol.
- 1Asset type and Asset.
- 2Protocol — the following fields change according to the protocol.
- 3IP address or name, Port and Device id (unit id) — the Modbus TCP fields.
- 4Advanced: Timeout (ms), Retries and Pause between requests (ms).
- 5Enabled — unchecked, the collector stops reading this asset without losing the points.
- 6Save and Cancel.
The fields of each protocol, with the value that comes filled in:
| Protocol | Fields |
|---|---|
| Modbus TCP | IP address or name · Port (502) · Device id (unit id) (1) |
| Modbus RTU (serial) | Serial port · Baud rate (9600) · Parity (N, E, O) (N) · Stop bits (1) · Device id (unit id) (1) |
| BACnet/IP | IP address or name · Port (47808) · Device instance |
| SNMP | IP address or name · Port (161) · Version (1 or 2c) (2c) · Community (public) |
| MQTT | IP address or name · Port (1883) · Use TLS · User · Password · Client id · Subscribed topics (one per line) |
| HTTP/JSON | Base URL · Method (GET) · Headers (Name: value, one per line) · Call every (s) (60) · Verify the certificate (checked) |
| Serial | Serial port · Baud rate (9600) · Parity (N, E, O) (N) · Stop bits (1) · Line ending |
| Ping (ICMP) | IP address or name |
| Advanced field | Default | What it is for |
|---|---|---|
| Timeout (ms) | 2000 | how long the collector waits for the equipment answer (from 100 to 60000) |
| Retries | 3 | how many times it repeats before considering the asset as not answering (from 0 to 10) |
| Pause between requests (ms) | 0 | minimum interval between two requests to the same equipment — useful for slow equipment or a shared serial line |
Once the link is saved, the Status column shows Waiting for the collector until the configuration goes down; then, Reading or No answer (with the error the collector reported, right below). A link with Enabled unchecked shows up as Disabled.
The same asset in two collectors
Section titled “The same asset in two collectors”An asset can be linked in more than one collector — for example, a switchboard with the multimeter on one network and the temperature sensor on another. H2O does not prevent it, but warns: on saving, Link saved. Note: this asset is also linked in … Each measurement accepts a single point.; and, in the asset row, in amber, Also linked in: with the name of the other collectors.
The points
Section titled “The points”The Points tab lists what the collector reads. The Points button of a row of the Equipment tab opens this tab already filtered by the asset.

Figure 7. The Points tab, filtered by the asset TR-01.
- 1The Asset filter — All assets or a linked asset.
- 2New point.
- 3Point column (the name) and Asset and measurement (the asset and, below it, the measurement that receives the value, with the unit).
- 4Address column: where the value is on the equipment.
- 5Type and conversion and Reading columns (how often and what is sent).
- 6Last value and Time columns.
- 7Status column: the quality of the last reading.
- 8Read now, Edit and Delete.
| Status | Meaning |
|---|---|
| Good | the value was read normally |
| Estimated | the value was calculated (average, sum) with readings missing in the period |
| Bad | the equipment answered with an error; the reading is not compared with the range |
| No communication | the equipment did not answer; there is no value |
| Not read yet | the point was created and no reading has arrived yet |
Below the measurement name, measurement inactive or deleted warns that the asset measurement was deactivated: the collector stops receiving that point until the measurement comes back. If the measurement is deleted in the asset, its points go with it.
Creating a point by hand
Section titled “Creating a point by hand”- On the Points tab, click New point. (Without any linked asset: Link an asset before creating points.)
- Choose the Linked asset and the Asset measurement. The Point name and the Unit come filled in with those of the measurement.
- In Address on the equipment, enter where the value is — the fields depend on the asset protocol.
- Adjust the Data type, the conversion and the reading. Click Save.

Figure 8. The New point form of an asset on Modbus TCP.
- 1Linked asset, Asset measurement and Point name.
- 2Address on the equipment: in Modbus, Table (holding, input, coil, discrete), Register (base 0), Number of registers and Bit (optional).
- 3Data type and Byte order.
- 4Scale (multiplies), Offset (adds), Formula (optional, with x) and Unit.
- 5Read every (s) and What to send.
- 6Enabled, Save and Cancel.
The point address in each protocol:
| Protocol | Address fields |
|---|---|
| Modbus TCP and Modbus RTU (serial) | Table (holding, input, coil, discrete) · Register (base 0) · Number of registers · Bit (optional) |
| BACnet/IP | Object type (e.g. analog-input) · Instance · Property (present-value) |
| SNMP | OID |
| MQTT | Topic · JSON path (e.g. $.energy.kwh) |
| HTTP/JSON | URL path · JSON path (e.g. $.energy.kwh) |
| Serial | Request sent · Expression to read the answer · Expression group |
| Ping (ICMP) | Field (disponivel or latencia_ms) — disponivel stores 1 when the equipment answers and 0 when it does not; latencia_ms, the response time |
| Field | What it is |
|---|---|
| Data type | how the value is stored on the equipment: bool, int16, uint16, int32, uint32, int64, float32, float64, bcd or string_num. 32- and 64-bit types take 2 or 4 Modbus registers — H2O adjusts the number by itself |
| Byte order | ABCD, CDAB, BADC or DCBA — it only matters for 32- and 64-bit types. An absurd value is almost always the wrong order or type |
| Scale (multiplies) | the number by which the value read is multiplied (e.g. 0.1 for a register in tenths) |
| Offset (adds) | the number added after the scale |
| Formula (optional, with x) | a calculation written with x, where x is the value already with the scale and the offset — for example (x-4)/16*100 for a 4 to 20 mA signal as a percentage |
| Unit | the unit of the value after the conversion |
| Read every (s) | the reading interval on the equipment, in seconds (default 60; from 1 to 86400) |
| What to send | Every reading, Average, Minimum, Maximum, Sum, Last value or Only on change |
| Window (s) | appears in Average, Minimum, Maximum and Sum: the period over which the collector calculates before sending (e.g. average of 300 s) |
| Minimum change | appears in Only on change: how much the value must vary to be sent (0 = any change) |
Read now
Section titled “Read now”Read now, in the point row, asks the collector to read that point right away and shows the result below the last value, in the line Value read:. The reading is not stored in the measurement history: it serves to check the address, the type and the scale before leaving it running.
| What appears | Meaning |
|---|---|
| Waiting for the collector… | the request is in the queue; the collector fetches the queue every 15 seconds |
| Read now: value and unit | the equipment answered — compare with the equipment display |
| no answer | the collector tried and the equipment delivered no value |
| The collector did not answer in time. | a minute passed without an answer — the collector has no contact or is busy |
| The reading failed. (or the error reported by the collector) | the collector refused or could not execute the request |
Map with AI
Section titled “Map with AI”The Map with AI button, in the row of the linked asset, builds the points from the manufacturer map. The screen explains: Enter the manufacturer and model. If you have the manufacturer map (MIB file, register spreadsheet or the manual PDF), send it: the AI reads it and proposes the points. Without a file, the AI drafts the typical measurements of the equipment. Nothing is saved before you review and apply.

Figure 9. The Point map with AI panel open for the asset UPS-02, before asking for the proposal.
- 1The title: the asset and the protocol of the link.
- 2Manufacturer and Model.
- 3Manufacturer map (optional) — MIB, spreadsheet, text or PDF, up to 10 MB.
- 4Notes for the AI (optional) — what you want to measure, what to leave out.
- 5Ask the AI for a proposal.
- Click Map with AI in the asset row. Fill in Manufacturer and Model and, if you have it, attach the file.
- Click Ask the AI for a proposal and wait — It may take up to a minute.
- Check the proposal table: select in the Use column what you want, correct the name and the address and choose the Asset measurement of each point.
- Click Read now to read the selected points from the equipment, before saving — the value appears in the Read now column.
- Click Apply N point(s).
| Proposal column | What it shows |
|---|---|
| Use | the box that decides whether the point goes in. It comes checked for points with an address and high or medium confidence |
| Point on the equipment | the name and the address, editable, and the AI note |
| Type and conversion | the data type, the scale and the unit |
| Asset measurement | Create: name (a New measurement) or a measurement that Already exists in the asset |
| Suggested range | for a new measurement, the normal and the critical range the AI suggests — or no suggestion |
| Reading | the interval and what is sent |
| Read now | the value read from the equipment when you click Read now |
| Confidence | High, Medium or Low |
The notice above the table says where the proposal came from:
| Source | Notice | What to check |
|---|---|---|
| MIB file | Proposal from file**:** N point(s) chosen among T objects of the file. The addresses (OID) come from the file, not from the AI. | whether the points chosen are the ones that matter |
| spreadsheet, text or PDF | Proposal from file**:** N point(s). Check the addresses against the manufacturer map. | the addresses, one by one, and the scale |
| no file | Draft without a file: N typical measurement(s) of the equipment. Fill in the addresses from the manual before applying; a point without an address is not created. | everything: it is only a list of what usually exists in this type of equipment |
Panel messages: Select at least one point. · Some selected points have no address. Fill in the address or uncheck them. · Select points with an address to read. · The file is large: the AI received N of T objects. · The AI could not build the proposal. Each application saves up to 40 points; for more, ask for another proposal.
Library model and copy from another asset
Section titled “Library model and copy from another asset”The Model button, in the row of the linked asset, opens the Model and copy panel, with three actions side by side.

Figure 10. The Model and copy panel of the asset UPS-02.
- 1The panel rule: A point whose address the asset already has is skipped. The measurement is matched by name with those of the asset; if it does not exist, it is created.
- 2Apply a model from the library: choose the model and click Apply model.
- 3Copy the points of another asset of this collector: choose the asset and click Copy points.
- 4Save the points of this asset as a model: Model name, Manufacturer, Model and Save as model.
| Action | When to use it | Rules |
|---|---|---|
| Apply model | the equipment is the same as one already mapped — at this or at another customer | only models of the same protocol as the link appear; with none, No models of this protocol in the library. |
| Copy points | there are several identical pieces of equipment on the same collector (ten meters of the same model): map one, copy to the others | only assets of this collector, with the same protocol and with points; with none, No other linked asset with the same protocol and with points. |
| Save as model | the map of this asset has already been checked and will be useful again | the name cannot repeat that of another model of the same protocol; without points, This asset has no points to store yet. |
When applying or copying, H2O reports the result: N point(s) created, M new measurement(s), S skipped because the asset already had them. Repeating the operation does not duplicate: a point whose address already exists in the asset is skipped.
The models are kept in Model library, a button on the Collectors screen.

Figure 11. The Model library.
- 1Import model — brings in a model exported from another environment.
- 2The Protocol filter.
- 3Model, Manufacturer and model, Protocol, Points and Site columns.
- 4Show points opens the list of points of the model; Export downloads the model as a file; Delete removes it.
Editing, disabling and unlinking
Section titled “Editing, disabling and unlinking”| Action | Where | Effect |
|---|---|---|
| Edit the link | Equipment tab | changes the address, the Advanced fields and Enabled. The protocol only changes without points |
| uncheck Enabled in the link | link form | the collector stops reading the asset; the points are kept. Status Disabled |
| Edit the point | Points tab | changes any field of the point. The linked asset does not change |
| uncheck Enabled in the point | point form | the collector stops reading only that point |
| Delete the point | Points tab — the button becomes Confirm | the point is removed; the readings already stored stay in the measurement |
| Unlink | Equipment tab — the button becomes Confirm: stops reading | the link and its points are removed: Asset unlinked. Readings already stored remain in the measurements. |